-40%
Accuenergy Acuvim IIR-D-5A-P1 Revenue Grade Power/Energy Meter, LCD, 5 A/1 A
$ 337.6
- Description
- Size Guide
Description
Untitled DocumentAccuenergy Acuvim IIR-D-5A-P1 Revenue Grade Power/Energy Meter, LCD, 5 A/1 A input, 415 Vac/300 Vdc
Model:
Acuvim IIR-D-5A-P1
| Order No:
Acuvim-IIR-D-5A-P1
Revenue grade power meter with data logging capabilites for single and three phase circuits features integrated on-board LCD display, field selectable 5 A or 1 A input for current transformers and wide range AC power supply input.
Brand:
Accuenergy
Model:
Acuvim IIR-D-5A-P1
Order No:
Acuvim-IIR-D-5A-P1
Condition:
NEW
Description
Accuenergy Acuvim IIR-D-5A-P1 Revenue Grade Power/Energy Meter, LCD, 5 A/1 A input, 415 Vac/300 Vdc
Accuenergy Acuvim IIR-D-5A-P1 Offers
The Accuenergy Acuvim IIR revenue-grade power/energy meter with data logging can be a powerful tool for monitoring the energy consumption of a property, which can provide both accurate billing for tenants while helping identify areas to implement energy efficiency upgrades. This model includes the Acuvim IIR basic unit with field selectable 5A or 1A current input, 100 to 415V AC, 50/60Hz, 100 to 300V DC power supply, and an integrated mounting option with LCD display.
Functions
Features
Revenue grade ANSI C12.20 class 0.2 & IEC 62053-22 class 0.2s
100ms refresh rate
Over/Under limit alarms
Web server and email sending
Switch status monitoring
Built-in MODBUS RTU via RS485 port
Can be upgraded to include Modbus TCP Ethernet, BACnet, Profibus, and a variety of other communication protocols and I/O expansions for added versatility
Onboard data logging memory is up to 8 MB and each log size is adjustable
Real time clock allows for any logged events to be accuratelytime stamped
Included
Accuenergy Acuvim IIR-D-5A-P1 Revenue Grade Power/Energy Meter, LCD, 5 A/1 A input, 415 Vac/300 Vdc
Specifications
Acuvim IIR Specifications
Accuracy
Acuvim-II
Accuracy
Acuvim-IIR/IIE/IIW
Resolution
Range
Voltage
0.2%
0.2%
0.1V
20V~1000kV
Current
0.2%
0.2%
0.1mA
5mA~50000A
Power
0.5%
0.2%
1W
-9999MW~9999MW
Reactive Power
0.5%
0.2%
1var
9999Mvar~9999Mvar
Apparent Power
0.5%
0.2%
1VA
0~9999MVA
Power Demand
0.5%
0.2%
1W
-9999MW~9999MW
Reactive Power Demand
0.5%
0.2%
1var
-9999Mvar~9999Mvar
Apparent Power Demand
0.5%
0.2%
0.2%
0~9999MVA
Power Factor
0.5%
0.2%
0.001
-1.000~1.000
Frequency
0.2%
0.2%
0.01Hz
45.00~65.00Hz
Energy Primary
0.5%
0.2%
0.1kWh
0-99999999.9kWh
Energy Secondary
0.5%
0.2%
0.001kWh
0-999999.999kWh
Reactive Energy Primary
0.5%
0.2%
0.1kvarh
0-99999999.9kvarh
Reactive Energy Secondary
0.5%
0.2%
0.001kvarh
0-999999.999kvarh
Apparent Energy Primary
0.5%
0.2%
0.1kVAh
0-99999999.9kVAh
Apparent Energy Secondary
0.5%
0.2%
0.001kVAh
0-999999.999kVAh
Harmonics
1.0%
1.0%
0.1%
0.0%~100.0%
20.0%~100.0% (IIR/IIE/IIW)
Phase Angle
2.0%
2.0%
0.1°
0.0°~359.9°
Unbalance Factor
2.0%
2.0%
0.1%
0.0%~100.0%
Running Time
0.01h
0~9999999.99h
Current Inputs (Each Channel)
Nominal Current
5A /1A
Metering Range
0~10A AC
Withstand
20Arms continuous,
100Arms for 1 second, non-recurring
Burden
0.05VA (typical) @ 5Arms
Pickup Current
0.1% of nominal
Accuracy
0.2% full scale
Voltage Inputs (Each Channel)
Nominal Full Scale
400V AC L-N, 690V AC L-L (+20%)
Withstand
1500V AC continuous
2500V AC, 50/60Hz for 1 minute
Input Impedance
2Mohm per phase
Metering Frequency
45Hz~65Hz
Pickup Voltage
10V AC (30V AC for Acuvim IIR/IIE/IIW)
Accuracy
0.2% full scale
Energy Accuracy (Acuvim IIR/IIE/IIW)
Active
According to IEC 62053-22: Class 0.2s
According to ANSI C12.20: Class 0.2s
Reactive (according to IEC 62053-23)
Class 2
Harmonic Resolution
Metered Value
Acuvim II: 31st harmonic
Acuvim IIR/IIE/IIW: 63rd harmonic
Control Power
Universal
AC or DC
Operating Range
100~415V AC, 50/60Hz
100~300V DC
Burden
5W
Frequency
50/60Hz
Withstand
3250V AC, 50/60Hz for 1 minute
Installation Category III (Distribution)
Low Voltage DC Control Power (Optional)
Operating Range
20~60V DC
Burden
5W
Communication
Rs-485 (standard)
MODBUS® RTU Protocol, 2-wire connection
1200~38400 baud rate
The second Rs-485 Port (Optional)
MODBUS® RTU Protocol, 2-wire connection
4800~38400 baud rate
Ethernet (Optional)
10M/100M BaseT
MODBUS® TCP/IP Protocol
Data Browsing through HTTP
Sending e-mail automatically
PROFI-BUs (Optional)
PROFIBUS-DP/V0 Protoco
Work as PROFIBUS slave, baud rate adaptive, up to 12M
Typical input bytes: 32, typical output bytes: 32
PROFIBUS standard according to EN 50170 vol.2
Terms & Conditions
Item Condition:
Unless specified otherwise all products listed are Brand New in the original factory packaging and include a full factory warranty.
Shipping:
We currently only ship to U.S. buyers. We ship items within one or two business days from payment. We do not process shipments on weekends and holidays. Local pick up is not available. We only ship to addresses verifiable by either PayPal or credit card issuing bank.
Please note that we cannot alter the address once a purchase is made. In the case of PayPal payment, we will ship orders when the payment is marked “Eligible” for PayPal Seller’s protection.
*Shipping Rates are for Continental US, Please Contact us for other US Destinations
Payment:
Currently all payments must be made directly though PayPal
Sales Tax:
We are required to charge sales tax in North Carolina
Return Policy:
If for any reason you are not 100% satisfied with a product you receive from us, you may return the regular stock product within 30 days from the time of receipt, for a full refund or exchange of the product you purchased (less any shipping costs). Within this time, products may be returned; freight prepaid and must be in their original packaging and in resalable condition.
Shipping errors, missing items or damages must be reported to us immediately (damages should be accompanied by a signed bill of lading acknowledging the damage). Items returned will be inspected for damage or misuse at which time they may be subject to restocking fees, other fees or refused, prior to the issuance of any credit.